Joint shear resistance
Adhesion c·f_ctd, friction μ·σ_n, and the joint reinforcement ρ·f_yd·(μ·sin α + cos α) to Eq. (6.25), with the German NA raise to 1.2·μ.
Privacy settings
We use Microsoft Clarity to understand how CALC is used — only if you agree. Necessary cookies keep the app working (sign-in, security, free-quota enforcement) and are always active.

SKL-000077 · Skill
EN 1992-1-1:2004+AC:2010, 3.1 Table 3.1, 6.2.2(6), 6.2.5DIN EN 1992-1-1/NA:2013-04 (content per Synopse 2010-02) + NA/A1:2015-12, NDP zu 3.1.6(1)P and (2)P, NDP zu 6.2.2(6), NCI zu 6.2.5(1) to (5)NABau Auslegung Nr. 2 (2019) to NCI zu 6.2.5(5)Enter the shear force, the joint width, the lever arm or effective depth, the concrete, the joint surface, and the joint reinforcement. Mia checks the joint to EN 1992-1-1, 6.2.5, with the CEN recommended values or the German National Annex, and shows adhesion, friction, reinforcement, and upper limit with their clauses.
Mia guides you step by stepShe guides you through the inputs and explains the results.
Check the interface shear to EN 1992-1-1:2004+AC:2010 with DIN EN 1992-1-1/NA:2013-04 + NA/A1:2015-12. Precast beam with cast-in-place topping, VEd = 115 kN, β = 1.0, joint width bi = 300 mm, effective depth d = 500 mm, C30/37, rough joint, joint reinforcement as = 500 mm²/m at 90°, B500, σn = 0, static loading.
Deterministic values of the calculation core for the stated inputs; z = 0.9·d = 450 mm calculated, reinforcement term raised to 1.2·μ (NCI zu 6.2.5(1)).
These templates prefill the form with typical inputs. They are not calculated results; the calculation runs in CALC.
Adhesion c·f_ctd, friction μ·σ_n, and the joint reinforcement ρ·f_yd·(μ·sin α + cos α) to Eq. (6.25), with the German NA raise to 1.2·μ.
The upper limit 0.5·ν·f_cd, with ν from Eq. (6.6N) or from the joint surface under the German NA.
The joint reinforcement a_s in mm²/m that the resistance check requires.
Normative basis
Frequently asked questions
By default z = 0.9·d from the effective depth of the composite section. Enter z directly when the joint reinforcement is also shear reinforcement; the German NA then requires z per NCI zu 6.2.3(1).
The German NA sets ν = 0 for a very smooth joint without external compression, so no shear transfer is admissible. Under external compression the friction term may be used up to μ·σn ≤ 0.1·fcd; this path is calculated only when you switch on the option for very smooth joints, otherwise Mia names it for a check by hand.
The recommended values halve the adhesion term c; the German NA sets c = 0 and requires at least a rough joint. The fatigue check of the joint reinforcement itself is not part of this check.
ACI 318 is handled by the separate skill Interface shear | ACI 318. This skill calculates EN 1992-1-1 only.
Start with the example and adapt it to your structural system.
New calculation