Design · Masonry

Capacity reduction factor at top or bottom of wall

  • Type: Coefficient
  • Version 1
  • reviewed on 11/13/2026

Capacity reduction factor at the top or bottom of an unreinforced masonry wall: Φi = 1 - 2 · ei / t.

Φi=1−2⋅eit\displaystyle \Phi_{i} = 1 - 2 \cdot \frac{e_{i}}{t}
Apply in CALC

Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.

eitΦi

Formula and quantities

SymbolNameUnitNote
ei\displaystyle e_{i}Design eccentricity at top or bottom of wallmmei\displaystyle e_{i} ≥ 0
t\displaystyle tThickness of wallmmt\displaystyle t > 0
Φi\displaystyle Φ_{i}End reduction factor–Result

Valid if2⋅ei<t\displaystyle 2 \cdot e_{i} < t

Worked example

ei\displaystyle e_{i} = 36 mm · t\displaystyle t = 240 mm

Φi\displaystyle Φ_{i} = 0.7 · Source: hand calculation

Scope and standard

EN 1996-1-1, clause 6.1.2.2 (valid for e_i < t / 2).

Standard
EN 1996-1-1-2005-a1:2012, clause 6.1.2.2, Eq. (6.4)
Result
Φi\displaystyle Φ_{i} (dimensionless)

Reference to clause and equation, no standard text. The description is written in our own words.