Design · Concrete

Concrete thermal conductivity upper limit (EN 1992-1-2)

  • Type: Property
  • Version 1
  • reviewed on 11/21/2026

Upper limit of thermal conductivity of normalweight concrete as a function of temperature (20°C to 1200°C) according to EN 1992-1-2 Clause 3.3.3 Eq. (3.1): λc = 2.0 - 0.2451 · (Θ / 100) + 0.0107 · (Θ / 100)².

λc=2.0−0.2451⋅Θ100+0.0107⋅(Θ100)2\displaystyle \lambda_{\mathrm{c}} = 2.0 - 0.2451 \cdot \frac{\Theta}{100} + 0.0107 \cdot \left(\frac{\Theta}{100}\right)^2
Apply in CALC

Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.

λc

Formula and quantities

SymbolNameUnitNote
Θ\displaystyle \ThetaConcrete temperature (20 to 1200 °C)1
λc\displaystyle \lambda_{\mathrm{c}}Thermal conductivity of concrete (in W/(m*K))1Result

Worked example

Θ\displaystyle \Theta = 500 1

λc\displaystyle \lambda_{\mathrm{c}} = 1.042 1

Standard and source

Result
λc\displaystyle \lambda_{\mathrm{c}} in 1

Reference to clause and equation, no standard text. The description is written in our own words.

Try it

λc\displaystyle \lambda_{\mathrm{c}} = 1.042 1= 2.0 - 0.2451 · ((500 1) / 100) + 0.0107 · ((500 1) / 100)²