Basic prestress transmission length lpt (EN 1992-1-1)
Basic value of the transmission length for pre-tensioned tendons according to EN 1992-1-1 Clause 8.10.2.2(2) Eq. (8.16): lpt = α1 · α2 · φ · σpm0 / fbpt.
Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.
Formula and quantities
| Symbol | Name | Unit | Note |
|---|---|---|---|
| Release method factor (1.0 gradual, 1.25 sudden) | 1 | ||
| Tendon cross-section factor (0.25 circular, 0.19 7-wire strand) | 1 | ||
| Nominal tendon diameter | mm | ||
| Initial tendon stress immediately after transfer | N/m² | ||
| Constant transfer bond stress | N/m² | ||
| Basic transmission length | mm | Result |
Worked example
= 1 · = 0.19 · = 12.5 mm · = 1,300,000,000 N/m² · = 5,760,000 N/m²
= 536.024 mm
Standard and source
- Standard
- EN 1992-1-1:2004
- Result
- in mm
Reference to clause and equation, no standard text. The description is written in our own words.