时变预应力损失(徐变、收缩、松弛) Δσ,p,c+s+r (EN 1992-1-1)

  • 类型:属性
  • 版本1
  • 2026/11/25已审核

根据 EN 1992-1-1 第 5.10.6(2) 条式 (5.46) 的混凝土徐变、收缩与预应力筋松弛综合时变预应力损失:Δσp,c+s+r = (epscs · Ep + 0.8 · Δσpr + (Ep / Ecm) · φ · σc,QP) / (1 + (Ep / Ecm) · (Ap / Ac) · (1 + (Ac / Ic) · zcp²) · (1 + 0.8 · φ))。

Δσp,c+s+r=εcs⋅Ep+0.8⋅Δσpr+EpEcm⋅ϕ⋅σc,QP1+EpEcm⋅ApAc⋅(1+AcIc⋅zcp2)⋅(1+0.8⋅ϕ)\displaystyle \Delta\sigma_{p,c+s+r} = \frac{\varepsilon_{cs} \cdot E_{p} + 0.8 \cdot \Delta\sigma_{pr} + \frac{E_{p}}{E_{cm}} \cdot \phi \cdot \sigma_{\mathrm{c},QP}}{1 + \frac{E_{p}}{E_{cm}} \cdot \frac{A_{p}}{A_{\mathrm{c}}} \cdot \left(1 + \frac{A_{\mathrm{c}}}{I_{\mathrm{c}}} \cdot z_{cp}^2\right) \cdot (1 + 0.8 \cdot \phi)}
Apply in CALC

Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.

zcpΔσp,c+s+rApEp

Formula and quantities

SymbolNameUnitNote
epscs\displaystyle eps_{cs}估算干燥与自收缩应变(正值)1
Ep\displaystyle E_{p}预应力钢材弹性模量N/m²
Δσpr\displaystyle \Delta\sigma_{pr}预应力筋松弛引起的应力损失N/m²
Ecm\displaystyle E_{cm}混凝土割线弹性模量N/m²
ϕ\displaystyle \phi混凝土徐变系数1
σc,QP\displaystyle \sigma_{\mathrm{c},QP}准永久荷载下预应力筋重心处的混凝土应力N/m²
Ap\displaystyle A_{p}预应力筋截面积mm²
Ac\displaystyle A_{\mathrm{c}}混凝土截面积mm²
Ic\displaystyle I_{\mathrm{c}}混凝土截面惯性矩mm⁴
zcp\displaystyle z_{cp}混凝土截面形心与预应力筋之间的距离mm
Δσp,c+s+r\displaystyle \Delta\sigma_{p,c+s+r}时变预应力应力损失N/m²Result

实例

epscs\displaystyle eps_{cs} = 0.0003 · Ep\displaystyle E_{p} = 195,000,000,000 N/m² · Δσpr\displaystyle \Delta\sigma_{pr} = 40,000,000 N/m² · Ecm\displaystyle E_{cm} = 35,000,000,000 N/m² · ϕ\displaystyle \phi = 2 · σc,QP\displaystyle \sigma_{\mathrm{c},QP} = 8,000,000 N/m² · Ap\displaystyle A_{p} = 1,500 mm² · Ac\displaystyle A_{\mathrm{c}} = 300,000 mm² · Ic\displaystyle I_{\mathrm{c}} = 22,500,000,000 mm⁴ · zcp\displaystyle z_{cp} = 350 mm

Δσp,c+s+r\displaystyle \Delta\sigma_{p,c+s+r} = 150,868,000 N/m²

Standard and source

Result
Δσp,c+s+r\displaystyle \Delta\sigma_{p,c+s+r} in MPa

Reference to clause and equation, no standard text. The description is written in our own words.

Try it

Unit system
Δσp,c+s+r\displaystyle \Delta\sigma_{p,c+s+r} = 150,868,000 N/m²= ((0.0003 1) · (195,000,000,000 N/m²) + 0.8 · (40,000,000 N/m²) + ((195,000,000,000 N/m²) / (35,000,000,000 N/m²)) · (2 1) · (8,000,000 N/m²)) / (1 + ((195,000,000,000 N/m²) / (35,000,000,000 N/m²)) · ((1,500 mm²) / (300,000 mm²)) · (1 + ((300,000 mm²) / (22,500,000,000 mm⁴)) · (350 mm)²) · (1 + 0.8 · (2 1)))

Continue with Mia

Fills the input field in CALC; nothing is sent until you send it.

No matching formula yet? Find the right calculation rule.

Describe what you want to determine. Mia searches the formula catalog first and clarifies assumptions before anything is calculated.

检索将在 设计 › 混凝土 开始。

Miaknows the formula catalog and asks for what is missing.

You clarify missing information with Mia in the next step. Nothing is calculated yet.