설계 · 강재
볼트의 설계 인장 저항 Ft,Rd
볼트의 설계 인장 저항: Ft,Rd = k2 · fub · As / γM2.
Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.
Formula and quantities
| Symbol | Name | Unit | Note |
|---|---|---|---|
| 볼트 계수 | – | ||
| 볼트의 극한 인장강도 | N/mm² | ||
| 볼트의 인장 유효단면적 | m² | ||
| 접합부에 대한 부분계수 | – | ||
| 설계 인장 저항 | kN | Result |
예제
= 0.9 · = 800 N/mm² · = 0.000245 m² · = 1.25
= 141.12 kN · Source: EN 1993-1-8:2005 Tabelle 3.4
Scope and standard
EN 1993-1-8 표 3.4에 따른 인장 볼트 접합부 (표준 볼트의 경우 k_2 = 0.9).
- Standard
- EN 1993-1-8:2005, 3.6.1 절, 식 Tabelle 3.4
- Result
- in kN
Reference to clause and equation, no standard text. The description is written in our own words.
Try it
Continue with Mia
Fills the input field in CALC; nothing is sent until you send it.
No matching formula yet? Find the right calculation rule.
Describe what you want to determine. Mia searches the formula catalog first and clarifies assumptions before anything is calculated.
설계 › 강재에서 검색이 시작됩니다.
Miaknows the formula catalog and asks for what is missing.