設計 · コンクリート構造
円形柱に対するパンチングせん断の基本管理周長
直径Dの円形柱から2d離れた位置の基本管理周長u1:u1 = π × (D + 4 × d)。
Catalog formula, not a design. Check input values, coefficients, and limits against the standard and its national annex.
Formula and quantities
| Symbol | Name | Unit | Note |
|---|---|---|---|
| 円形柱の直径 | m | ||
| スラブの平均有効深さ | m | ||
| 基本管理周長 | m | Result |
例題
= 0.4 m · = 0.2 m
= 3.76991 m · Source: EN 1992-1-1:2004 条項 6.4.2 (1)
Scope and standard
内部位置で円形柱に支持されたフラットスラブ(EN 1992-1-1 6.4.2項)。
- Standard
- EN 1992-1-1:2004、6.4.2 (1)項
- Result
- in m
Reference to clause and equation, no standard text. The description is written in our own words.